BENSHAW ENHANCED KEYPAD Manuel d'utilisateur Page 118

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 182
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 117
110
Com Parity I/O 46
Com Drop # I/O 47
I/O: Com Parity
46 RTU N81
I/O: Comm Drop #
47 1
7 - PARAMETER DESCRIPTION
LCD Display
Range
LCD Display
Range 1 to 247 (Default 1)
Description This parameter sets the drop number of the serial communication port. A change will not take effect until
the power is cycled.
Parameter Value
Function
RTU N81 (Default) No parity, 8 data bis, 1 stop bit
RTU N82 No parity, 8 data bits, 2 stop bits
RTU E81 Even parity, 8 data bits, 1 stop bit
RTU O81 Odd parity, 8 data bits, 1 stop bit
Description This parameter sets the parity and stop bits recognized by the serial communication port.
See also DRV 05, 07 on page 78.
Com Baudrate I/O 48
I/O: Com Baudrate
48 9600
LCD Display
Range
Parameter Value Baud Rate Assigned
4800 4800 bps
9600 (Default) 9600 bps
19200 19.2 K bps
38400 38.4 K bps
57600 57.6 K bps
Description This parameter sets the baud rate for serial communication.
z NOTE: Only available for Modbus communication.
z NOTE: The baud rate changes will not take effect until power is cycled