BENSHAW ENHANCED KEYPAD Informations techniques Page 147

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 174
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 146
9 – TECHNICAL INFORMATION
Technical Specifications
141
9.6 List of Motor Protection Features
ANSI 51 – Electronic motor overload (Off, class 1 to 40, separate starting and running curves available)
ANSI 86 – Overload lockout
ANSI 51 – Overcurrent detection (Off or 50 to 800% and time 0.1 to 90.0 sec. in 0.1 sec. intervals)
ANSI 50 - Instantaneous electronic overcurrent trip
ANSI 37 – Undercurrent detection (Off or 5 to 100% and time 0.1 to 90.0 sec. in 0.1 sec. intervals)
ANSI 46 – Current imbalance detection (Off or 5 to 40%)
ANSI 51G – Ground fault detection (Off or 5 to 100%)
ANSI 48 – Adjustable up-to-speed / stall timer (1 to 900 sec. in 1 sec. intervals)
ANSI 59 / 27 – Adjustable over/under voltage protection (Off or 1 to 40%, time 0.1 to 90.0 sec. in 0.1 sec. intervals,
independent over and under voltage levels)
ANSI 47 - Phase rotation (selectable ABC, CBA, Insensitive, or Single Phase)
ANSI 81 – Over / Under Frequency
ANSI 74 – Alarm relay output available
Single Phase Protection
Shorted SCR detection
Vue de la page 146
1 2 ... 142 143 144 145 146 147 148 149 150 151 152 ... 173 174

Commentaires sur ces manuels

Pas de commentaire